DPT (with 2 relays for 24 V)
Robust, universal, industrial-grade Δp - FILTER - CONTROL device with good long-term stability, very low temperature drift and high overpressure safety. 4 linear short circuit-proof analogue outputs 0-10 V, 2-10 V, 0-20 mA, 4-20 and 2 potential-free relay outputs for limit values max / min, are fitted as standard.
Examples: Ventilation and air-conditioning units, medical technology, clean room technology, filter control, fill level control and regulation, flow detection system, etc.
For ventilation applications with the ever present turbulence, a programmable Δp damping of the display and outputs is a necessary functional advantage.
Features
Differential pressure, relative pressure (positive or negative pressure)
Measuring ranges: 0 - 0.4 mbar to 0 - 10 bar available
10 device groups with user-programmable ∆p measuring range within the measuring span of one group:
Group 1: 0 - 0.4 mbar to 0 - 2 mbar
Group 2: 0 - 1 mbar to 0 - 5 mbar
Group 3: 0 - 2 mbar to 0 - 10 mbar
Group 4: 0 - 10 mbar to 0 - 50 mbar
Group 5: 0 - 20 mbar to 0 - 100 mbar
Group 6: 0 - 100 mbar to 0 - 500 mbar
Group 7: 0 - 200 mbar to 0 - 1000 mbar
Group 8: 0 - 1 bar to 0 - 5 bar
Group 9: 0 - 2 bar to 0 - 10 bar
Group 10: 0-5 to 0-25 mbar
Pressure sensor highly overloadable
Pressure sensor temperature compensated
Integrated filters in the pressure connections
Adjustable Δp-damping as standard: 1-240s
Extreme ambient temperature range -20 °C to +60 °C (4°F to +140°F)
4 analogue outputs as standard: 0-10V, 2-10V, 0-20mA, 4-20mA, linear, short-circuit-proof
2 relay outputs as standard, switching voltage 24 VDC
Supply voltage: 24 VDC or universal 24 VDC and 115-120/230-240 V, 50-60 Hz available
Housing protection class IP 65, ABS plastic
Documentation