Filtration - Valve - Controller

Industrial process gases and exhausts are often cleaned in different processes by tissue filters. Our Filtration-Valve-Controller of the types RFS*.. TFS*.. IF*.. as well as the Filtration-Valve-Controller with integrated Differential Pressure Regulator of the types DFS, are produced for the electric control of magnet valves in the industrial dedusting technology.
We offer the complete program of the automation, for new plants as well as for efficiency increase of existing tissue filters.
Our Filtration-Valve-Controller for large plants consists of the types DFS* - Master und TFS*-E – Slave.
According to the plant capacity the necessary number of Slave-Controllers TFS are connected at the Master-Controller DFS, via a BUS-system. One Slave-Control is associated with one filter-chamber. With this flexible concept we can customize our devices to any number of filter-chambers and valves. Please take the detailed functions from the following product descriptions as well as from the PDF-datasheets.

 
RELAY - FILTER - SCANNER TYPE: RFS*91
6.1
Filter - Valve - Control unit, 10 relay outputs, expansion possible  


 

- max. 10 relay outputs for filter valves, programmable (3 - 10)
- Expansion function : extension with RELAY-FILTER-SCANNERs, if required
- PULSE : 50 ms - 10 s
- INTERVAL 1 : 1 s - 120 s
- INTERVAL 2 : 1 s - 480 s, can be switched off
- ALARM-contact to indicate: ‘no voltage / power OFF’
- Case with EX-protection available, ATEX conform

 
TRANS - FILTER - SCANNER TYPE: TFS*20-S
6.2
Filter - Valve - Control unit, 20 outputs 24 VDC  

  - max. 20 filter valve outputs, programmable: 11 - 20, 24 V-, 23 - 46 W, short circuit-safe
- Pulse : 20 ms - 10 s
- Interval : 5 s - 60 s x1, x2, x8, x16 programmable
- ALARM-contact to indicate: ‘no voltage / power OFF’
- Expansion-Relaycontact for more than 20 valveoutputs with additional units TFS20-S-E
- Case with EX-protection available, ATEX conform
 
TRANS - FILTER - SCANNER TYP: TFS*20-S-ALU-EX
6.3
Filter - Valve - Control unit, 20 outputs 24 VDC  

  - max. 20 filter valve outputs, programmable: 11 - 20, 24 V-, 23 - 46 W, short circuit-safe
- Pulse : 20 ms - 10 s
- Interval : 5 s - 60 s x1, x2, x8, x16 programmable
- ALARM-contact to indicate: ‘no voltage / power OFF’
- Expansion-Relaycontact for more than 20 valveoutputs with additional units TFS20-S-E
- Cases with EX-protection, ATEX conform
 
TRANS - FILTER - SCANNER TYPE: TFS*73Q-E
6.4
Filter - Valve - Control extension unit, 25 outputs 24 VDC  

  - max. 25 filter valve outputs, 24 VDC, 23 W or 46 W
- Valve CONTROL : wire break, short circuit
- Extension function : extension with TRANS-FILTER-SCANNER TFS*73Q-E, if required
- Housings with EX-protection available, conform ATEX
 
Filtration - Valve - Controller
 
FILTER - SCANNER TYP: IF*6
6.5
Filter - Valve - Control unit with purification, 6 outputs 24 VDC  

 

- 6 filter valve outputs, programmable: 1 - 6, 24 V-, 23 - 46 W, short circuit-safe
- Pulse : 20 ms - 10 s
- Interval : 5 s - 60 s x1, x2, x8, x16, programmable
- input for p-switch or p-regulator connection
- ALARM-contact to indicate: ‘no voltage/power OFF’
- Case with EX-protection ATEX conform available

 
p - CONTROL-FILTER-SCANNER TYP: DFS*12-AB
6.6
Mini Filter-Valve-Control unit with p-Controller, 4 valve outputs with relay contacts
Filter-Ventil-Steuerung mit p-Regler, 12 Ventilausgänge
 

 

- Pressure ranges: 0 - 2 mbar up to 0 - 1000 mbar
- 4 filter valve outputs with relay contacs and a long term stability. The number of
- valveoutputs is programmable
- Pressure sensor overload-safe and temperature compensated,
- with manuel zeropoint calibration function
- Programmable p-ranges by the user are possible, within the 3 unit-groups:
- Group 1 : 0 - 2 mbar up to 0 - 10 mbar
- Group 2 : 0 - 20 mbar up to 0 - 100 mbar
- Group 3 : 0 - 200 mbar up to 0 - 1000 mbar
- p-Damping, programmable : ca. 0 s up to 240 s
- PULSE 1 - 4 : 20 ms - 5 s, separately programmable for each INTERVAL 1 - 4
- INTERVAL 1 : 5 s - 240 s
- INTERVAL 2 : 5 s - 60 min
- INTERVAL 3 : 5 s - 240 s
- INTERVAL 4 for I-C-C : 5 s - 240 s
- 4 p-set points are programmable: CONTROL min, CONTROL max,
- CONTROL above-max, I-C-C

- Programmable minimum signal period from 3 s - 999 s for the p-set points
- Programmable delay time from 1 s - 999 s for the p-set points
- INTENSIVE-CLEANING-CYCLE I-C-C, programmable 1 - 200 cycles
- Analogue output 0-10 V, 0-20 mA or 2-10 V, 4-20 mA, short-circuit safe

- Housing protection class IP65. Ex-protection conform ATEX available.

 
p - CONTROL-FILTER-SCANNER TYP: DFS-73Q*AB
6.7
Filter-Valve-Control unit with p-Controller, 25 valve outputs 24 VDC, extension possible
also available as external controlable by buttons
 

 

- Pressure ranges: 0 - 2 mbar up to 0 - 1000 mbar
- max. 25 filter valve outputs, 24 VDC loadable with 46 W e.g. 50 valves with 23 W
- Extension function : extension with TFS-73 TRANS-FILTER-SCANNER
- Pressure sensor overload-safe, temperature compensated,
- and manuel zeropoint calibration
- Programmable p-ranges by the user are possible, within the 3 unit-groups:
- Group 1 : 0 - 2 mbar up to 0 - 10 mbar
- Group 2 : 0 - 20 mbar up to 0 - 100 mbar
- Group 3 : 0 - 200 mbar up to 0 - 1000 mbar
- p-Damping, programmable : ca. 0 s up to 240 s
- Valve - control : wire break, short circuit, no JET-air-pulses
- PULSE 1 - 4 : 20 ms - 5 s, separately programmable for each INTERVAL 1 - 4
- INTERVAL 1 : 5 s - 240 s
- INTERVAL 2 : 5 s - 60 min
- INTERVAL 3 : 5 s - 240 s
- INTERVAL 4 for I-C-C : 5 s - 240 s
- 6 p-set points are programmable: CONTROL min, CONTROL max,
- CONTROL above-max, I-C-C, ALARM min and ALARM max

- Programmable minimum signal period from 3 s - 999 s for the p-set points
- Programmable delay time from 1 s - 999 s for the p-set points
- INTENSIVE-CLEANING-CYCLE I-C-C, programmable 1 - 200 cycles
- Signal inputs for remote control: HAND , I-C-C, STOP
- Analogue output 0-10 V, 0-20 mA or 2-10 V, 4-20 mA, short-circuit safe
- 2 types of housings: AB or PG. EX-protection conform ATEX available.
- Option: Analogue input 4-20 mA for external p-Transmitter DMC*

 
p - CONTROL-FILTER-SCANNER TYP: DFS-73Q*PG
6.8
Filter-Valve-Control unit with p-Controller, 25 valve outputs 24 VDC, extension possible
also available as external controlable by buttons
 

 

- Pressure ranges: 0 - 2 mbar up to 0 - 1000 mbar
- max. 25 filter valve outputs, 24 VDC loadable with 46 W e.g. 50 valves with 23 W
- Extension function : extension with TFS-73 TRANS-FILTER-SCANNER
- Pressure sensor overload-safe, temperature compensated
- and manual zeropoint calibration
- Programmable p-ranges by the user are possible, within the 3 unit-groups:
- Group 1 : 0 - 2 mbar up to 0 - 10 mbar
- Group 2 : 0 - 20 mbar up to 0 - 100 mbar
- Group 3 : 0 - 200 mbar up to 0 - 1000 mbar
- p-Damping, programmable : ca. 0 s up to 240 s
- Valve - control : wire break, short circuit, no JET-air-pulses
- PULSE 1 - 4 : 20 ms - 5 s, separately programmable for each INTERVAL 1 - 4
- INTERVAL 1 : 5 s - 240 s
- INTERVAL 2 : 5 s - 60 min
- INTERVAL 3 : 5 s - 240 s
- INTERVAL 4 for I-C-C : 5 s - 240 s
- 6 p-set points are programmable: CONTROL min, CONTROL max,
- CONTROL above-max, I-C-C, ALARM min and ALARM max

- Programmable minimum signal period from 3 s - 999 s for the p-set points
- Programmable delay time from 1 s - 999 s for the p-set points
- INTENSIVE-CLEANING-CYCLE I-C-C, programmable 1 - 200 cycles
- Signal inputs for remote control: HAND , I-C-C, STOP
- Analogue output 0-10 V, 0-20 mA or 2-10 V, 4-20 mA, short-circuit safe

- 2 types of housings: AB or PG. EX-protection conform ATEX available.
- Option: Analogue input 4-20 mA for external p-Transmitter DMC*

 
Filtration - Valve - Controller
 
p-CONTROL-FILTER-SCANNER TYP: DFS-73Q*AL-Ex-Zone 21
6.9

Filter-Valve-Control unit with p-Controller, 25 valve outputs 24 VDC, extension possible

 

 

- 25 filter valve outputs, 24 VDC loadable with 46 W e.g. 50 valves with 23 W
- Extension function : extension with TFS-73 TRANS-FILTER-SCANNER
- Pressure sensor overload-safe and temperature compensated,
- and with manual zero point calibration function
- Programmable p-ranges by the user are possible, within the 3 unit-groups:
- Group 1 : 0 - 2 mbar up to 0 - 10 mbar
- Group 2 : 0 - 20 mbar up to 0 - 100 mbar
- Group 3 : 0 - 200 mbar up to 0 - 1000 mbar
- p-Damping, programmable : ca. 0 s up to 240 s
- Valve - control : wire break, short circuit, no JET-air-pulses
- PULSE 1 - 4 : 20 ms - 5 s, separately programmable for each INTERVAL 1 - 4
- INTERVAL 1 : 5 s - 240 s
- INTERVAL 2 : 5 s - 60 min
- INTERVAL 3 : 5 s - 240 s
- INTERVAL 4 for I-C-C : 5 s - 240 s
- 6 p-set points are programmable: CONTROL min, CONTROL max,
- CONTROL above-max, I-C-C, ALARM min and ALARM max

- Programmable minimum signal period from 3 s - 999 s for the p-set points
- Programmable delay time from 1 s - 999 s for the p-set points
- INTENSIVE-CLEANING-CYCLE I-C-C, programmable 1 - 200 cycles
- Signal inputs for remote control: HAND , I-C-C, STOP
- Analogue output 0-10 V, 0-20 mA or 2-10 V, 4-20 mA, short-circuit safe
- EX-protection conform ATEX Zone 21 available with push-buttons into the cover

- Option: Analogue input 4-20 mA for external p-Transmitter DMC*

 
p-CONTROL-FILTER-SCANNER TYP: DFS-73Q*AL-Ex-Zone 22
6.10
Filter-Valve-Control unit with p-Controller, 25 valve outputs 24 VDC, extension possible
also available as external controlable by buttons
 

 

- 25 filter valve outputs, 24 VDC loadable with 46 W e.g. 50 valves with 23 W.
- The number of valve outputs is programmable
- Extension function : extension with TFS-73 TRANS-FILTER-SCANNER
- Pressure sensor overload-safe, temperature compensated,
- and manual zero point calibration
- Programmable p-ranges by the user are possible, within the 3 unit-groups:
- Group 1 : 0 - 2 mbar up to 0 - 10 mbar
- Group 2 : 0 - 20 mbar up to 0 - 100 mbar
- Group 3 : 0 - 200 mbar up to 0 - 1000 mbar
- p-Damping, programmable : ca. 0 s up to 240 s
- Valve - control : wire break, short circuit, no JET-air-pulses
- PULSE 1 - 4 : 20 ms - 5 s, separately programmable for each INTERVAL 1 - 4
- INTERVAL 1 : 5 s - 240 s
- INTERVAL 2 : 5 s - 60 min
- INTERVAL 3 : 5 s - 240 s
- INTERVAL 4 for I-C-C : 5 s - 240 s
- 6 p-set points are programmable: CONTROL min, CONTROL max,
- CONTROL above-max, I-C-C, ALARM min and ALARM max

- Programmable minimum signal period from 3 s - 999 s for the p-set points
- Programmable delay time from 1 s - 999 s for the p-set points
- INTENSIVE-CLEANING-CYCLE I-C-C, programmable 1 - 200 cycles
- Signal inputs for remote control: HAND , I-C-C, STOP
- Analogue output 0-10 V, 0-20 mA or 2-10 V, 4-20 mA, short-circuit safe
- EX-protection conform ATEX Zone 22
- Option: Analogue input 4-20 mA for external p-Transmitter DMC*

 